Switched PRO2 – User Guide
Using the Command Line Interface (CLI) • 164
Parameters
The set loadshed command uses the following parameters:
Sets to allow branch shedding events.
Sets to allow line shedding events.
Sets to allows sensor shedding events.
Sets to allow UPS shedding events.
Sub-Parameters
The set loadshed command uses the following sub-parameters:
Sheds outlets only when all UP devices on an upstream line go to “on
battery”.
Sheds outlets when any UPS device on an upstream line goes to “on
battery”.
The delay that a UPS device needs to be “on utility” before recovering
outlets. 0-10 minutes.
Shed outlets are not recovered Does not recover shed outlets when
even conditions are cleared.
Automatically recover shed outlets when event conditions are cleared.
The delay that a UPS device needs to be “on battery” before shedding
outlets. 0-10 minutes.
Usage Guidelines
The Smart Load Shedding feature must be enabled.
Command Access
Admin level only
set location
Sets the system location string.
Command Syntax
set location <location string>
Parameters
The set location command uses the following parameter:
Location string text for system location. 0-63 characters.
Command Access
Admin level only