Switched PRO2 – User Guide
Using the Command Line Interface (CLI) • 167
Sets an extra on delay when turning on an outlet. 0-900 seconds.
Sets the hostname for an outlet for script or shutdown actions.
0-63 characters.
Sets the hysteresis between event state and recovery.
Sets the current load for an outlet. min 0.0A, max (max current) in
show outlets command, hyst 1.0-10.0A (default 1.0A)
Sets if load shedding (due to outlet current load events) is allowed for
an outlet.
Sets if control actions are disabled for an outlet after wakeup state is
applied.
Sets the power factor. min 0.00, max 1.00, hyst 0.0-0.20 (default 0.02)
Sets an extra on delay when rebooting an outlet (5-600 seconds).
Sets to additionally send request to have shutdown agent run a script
before shutting down the host.
Sets the load shedding outlet control action for all sensor alarm events.
Sets the delay between turning on outlets. 0-15 seconds.
Sets if notification of pending off state of outlet is sent to outlet host
before changing state.
Sets the remote shutdown delay for an outlet. 1-900 seconds.
Sets if SNMP trap notifications for outlet events.
Sets if load shedding (due to temperature sensor events) is allowed for
an outlet.
Sets if load shedding (due to UPS events) are allowed for an outlet.
Sets the default outlet control state after system power up.
Sets if load shedding (due to water sensor events) is allowed for an
outlet
Sets the power (without power factor). min 0W, max (power capacity) in
ostat details, hyst 0-1000W (default 10W).