Switched PRO2 – User Guide
Using the Command Line Interface (CLI) • 166
set outlet
Sets outlet configuration values.
Command Syntax
set outlet branchevent [disabled | enabled] <name | id | ALL>
set outlet chglogging [disabled | enabled]
set outlet email [disabled | enabled] <name | id | ALL>
set outlet load [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set outlet load hyst <value>
set outlet name <name | id> <new name>
set outlet snmpt [disabled | enabled] <name | id | ALL>
set outlet watts [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set outlet watts hyst <value>
For Switched PRO2 products only:
set outlet extondelay <name | id | ALL> <value>
set outlet host <name | id> <hostname>
set outlet lock [disabled | enabled] <name | id | ALL>
set outlet rebootdelay <value>
set outlet script [disabled | enabled] <name | id | ALL>
set outlet script delay <name | id | ALL> <value>
set outlet seqdelay <value>
set outlet shutdown [disabled | enabled] <name | id | ALL>
set outlet shutdown delay <name | id | ALL> <value>
set outlet wakeup [on | off | last] <name | id | ALL>
For the enabled Smart Load Shedding feature:
set outlet contactevent [disabled | enabled] <name | id | ALL> <contact sensor name | id |
ALL>
set outlet lineevent [disabled | enabled] <name | id | ALL>
set outlet sensoraction [off | on]
set outlet tempevent [disabled | enabled] <name | id | ALL> <temp sensor name | id | ALL>
set outlet upsevent [disabled | enabled] <name | id | ALL>
set outlet waterevent [disabled | enabled] <name | id | ALL> <water sensor name | id |
ALL>
For AC products only:
set outlet pf [alarmlo | warnlo] <name | id | ALL> <value>
set outlet pf hyst <value>
Parameters
The set outlet command uses the following parameters: