Switched PRO2 User Guide
Using the Command Line Interface (CLI) 179
oidspoll
The OID for getting the “on battery”/“on utility” value when polling the
UPS by SNMP.
onbattery
Value of the OID when the UPS is in an “on battery” state. 1-65535.
onutility
Value of the OID when the UPS is in an “on utility” state. 1-65535.
port
Port number for polling the UPS by SNMP. 1-65535 (default 161).
type
Sets the type of the UPS; sets default commstr, oidspoll, onbattery,
onutility, and port. 1-11.
Sub-Parameters
The set ups command uses the following sub-parameter:
oid
The OID string with sequences of a dot and a number. 1-65535.
Command Access
Admin level only
set user
Sets configuration values for local user access rights.
Command Syntax
set user access [admin | ononly | poweruser | rebootonly | user | viewonly] <username>
set user password <username> {password} {verify password}
set user sysmon [disabled | enabled] <username>
Parameters
The set user command uses the following parameters:
access
Sets the access type of a local user.
Note: On-Only, Reboot-Only, and View-Only are available for Switched
PRO2 products.
password
Sets the password for a local user.
sysmon
Sets system monitor access for a local user.
Sub-Parameters
The set user command uses the following sub-parameter:
username
The ID of the local user to change access rights. 0-32 characters.
Command Access
Admin level only