EasyManua.ls Logo

Server Technology switched pro2 - Page 182

Server Technology switched pro2
213 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Switched PRO2 User Guide
Using the Command Line Interface (CLI) 182
show cords
Shows cord configuration values.
Command Syntax
show cords
Command Access
Admin level only
Example
Switched CDU: show cords
ID Cord Name
-- ---------
AA Master_Cord_A
BA Link_Cord_A
SNMP Email User / Factory User / Factory
ID Notif. Notif. Current Capacity Nominal Voltage
-- ------ ------ ---------------- ---------------
AA enabled enabled 30A / 30A 230V / 230V
BA enabled enabled 30A / 30A 230V / 230V
Power Power Power Power Balance Balance
ID Lo-Alrm Lo-Warn Hi-Warn Hi-Alrm Hi-Warn Hi-Alrm
-- ------- ------- ------- ------- ------- -------
AA 0W 0W 14490W 16560W 15% 20%
BA 0W 0W 14490W 16560W 15% 20%
App Pwr App Pwr App Pwr App Pwr PF PF
ID Lo-Alrm Lo-Warn Hi-Warn Hi-Alrm Lo-Alrm Lo-Warn
-- ------- ------- ------- ------- ------- -------
AA 0VA 0VA 14490VA 16560VA 0.70 0.80
BA 0VA 0VA 14490VA 16560VA 0.70 0.80
Common Cord Settings
Cord Power Hysteresis: 100
Cord Apparent Power Hysteresis: 100
Cord Power Factor Hysteresis: 0.0
Cord 3-Phase Out-Of-Balance Hyst: 2%

Table of Contents