Switched PRO2 User Guide
Using the Web Interface 81
Configuring Environmental Monitoring (EMCU) Thresholds
If an EMCU is connected to the PRO2 unit, the Sensors page will also allow configuration of water, contact closure
and analog-to-digital (ADC) voltage sensors to provide sensor name and SNMP/Email notifications.
In addition, for ADC voltage sensors only, high/low warning/alarm thresholds can be set. Water and contact closure
sensors can have either Normal or Alarm status there are no other states or value ranges.
To set ADC voltage sensor thresholds:
1. Click the ADC sensor thresholds link at the bottom of the Sensors page to display the configuration page:
2. Provide the threshold hysteresis between event state and recovery. Range is 0-20; default is 1.
3. Set the low/high alarm and low/high warning threshold values for the ADC sensor. Range is 0-255;
default is 0.
4. Click Apply.