Connecting AC Power
The P-2 can operate on any 100–277V, 50/60 Hz AC mains power supply. It draws approximately 1.2 amps at full power
(230V).
For permanent installation, have a qualified electrician wire the mains cable directly to a suitable branch circuit.
The junction’s ingress protection (IP) rating must be suitable for the location.
For temporary installation, the mains cable may be fitted with a grounded connector intended for exterior use.
The device must be grounded/earthed and be able to be isolated from AC power. The AC power supply must incorporate a
fuse or circuit breaker for fault protection.
After connecting the P-2 to power, run the on-board test, using the “TestSelftest” menu, to ensure that the device and
each LED are functioning correctly. See “Control menu” on page 39.
CAUTION: Do not open the device to replace the supplied power cable, or connect the device to an electrical dimmer system,
as this can damage it.
The power cable color coding is given in Table 1-1.
Connect the black wire to live
Connect the white wire to neutral
Connect the green/yellow wire to ground (earth)
Table 1-1
Color
Black
White
green/yellow
Conductor
live
neutral
ground (earth)
Symbol
or
L
N
Wire