Page #12 background imageLoading...
Page #12 background image
12(45)
Table 1-4Specifications List (2)
Model
Item/
Parameters
SIC-20W SIC-25W SIC-30W SIC-40W SIC-45W SIC-50W
Refrigerant
Capacity
1)1
kW 58.2 66 86 115.1 129 132
Kcal/hr 50,052 56,760 73,960 98,986 110,940 113,520
Compressor
output
power
kW
12.92 14.66 19 25.46 28.5 29.32
HP 20 25 30 40 45 50
Refrigerant
Weight (kg) 10 14 17 20 25 34
Control Mode Thermostatic expansion valve
Type R22
Evaporator Type Tube-in-shell style
Condenser
Type Tube-in-shell style
Inlet/outlet water
pipe (inch)
2
1
/
2
2
1
/
2
× 2
Cooling water
flow (L/min)
220 270 330 480 500 600
Water Tank Capacity (L) 270 700
Water pump 2)
(50Hz)
Power (kW) 2.2 / 3 / 4 4 / 3 / 4 4 / 4 / 5.5
Pump flow
(L/Min)
200 / 300 / 300 300 / 300 / 300 533 / 366 / 367
Pump pressure
(kgf/cm
2
)
2.5 / 3 / 4.2 2.7 / 3.4 / 4.3
Total Power (kW)
3)
15.12 16.86 23 29.46 32.5 33.32
Pipe
Coupling
(inch)
Chilled Water
Outlet
2 2
1
/
2
2
1
/
2
Chilled Water
Inlet
2 2
1
/
2
2
1
/
2
Water Tank
Outlet
1/2 1
Water Tank
Overflow Port
1/2 1
Protective
Devices
Compressor Overload relay
pump Overload relay
Chilling Water
Circuit
High and low pressure switch/anti-freeze switch
Water Circuit Flow switch (optional) / water tank level sensor (optional) / bypass valve
Power(VAC)
4
3Φ, 400VAC, 50HZ
Measures Exchange 1kW=860 kcal/hr 1RT=3,024kcal/hr 10,000Btu/hr=2,520kcal/hr
We reserve the right to change
specifications without prior noice.
Note:
1) Refrigeration capacity is measured based on the flow 0.172 m3 / (h.k W) and the outlet temperature (7)
of chilled water under the environment temperature of 35.
2) Low pressure pump is for domestic and Southeast Asia export, customers can change for medium
pressure pumps (use P for short; e.g.: SIC-5A-P) or high pressure pumps (use HP for short; e.g.:
SIC-5A-HP), specific parameters in turn as shown above.
3) Pump power is included in total power.
4) Special orders of machine voltage can be acceptable according to customers requests.