35(45)
4.5.1 Default parameter setting
Table 4-5:Default Parameter Setting
No. Code Meaning of parameter Default value Remark
1 st Set point of out 1 7 Unit: ℃
2 rd Temp. difference relative to out 1 2 Unit:℃
3 r1 Minimum value of st 7 Unit:℃
4 r2 Maximum value of st 35 Unit:℃
5 st2 Set point of out 2 2 Unit:℃
6 rd2 Temp. difference relative to out 2 2 Unit:℃
7 c2 Min. shutdown time of out 1 2 Unit :min
8 c3 Min. boot time of out 1 2 Unit:min
9 c22 Min. shut down time of out 2 3 Unit :min
10 c23 Min. boot time of out 2 2 Unit :min
11 c0 Min. start interval of out1 and out2
60 Unit :S
12 c1
Start delay of out1 after powering
on
2 Unit :min
13
AH
High- temp. alarm threshold value
/ deviation (AH=0; alarm disabled)
35 Unit:℃
AL
Low- temp. alarm threshold value /
deviation (AL =0; alarm disabled)
5 Unit:℃
14 Ad Temp. alarm shutdown delay 0 Unit :min
Note: 1.This parameter is only applicable to temperature controller PZXNS0G001 version. Do not use this
parameter for other models or versions.
4.5.2 Parameter setting method
When setting, press and hold the key for more than 3 secs, an adjustable
“PS” will appear on the screen. Press button and then the button to
enter the password 22. When setting parameters, it must press the key till
it returns to the temp. display interface. Otherwise, the set parameters will not be
saved.
Attention!
The parameter of the temperature controller has been set before delivery. Don’t set
the parameters unless otherwise specified.