Figure 1: SICK product ID
4 Mounting
Mount the sensorusing a suitable mounting bracket (see the SICK range of accesso‐
ries).
Note the maximum permissible tightening torque for the sensor of 0.4Nm.
5 Electrical installation
5.1 Notes on electrical installation
NOTICE
Equipment damage due to incorrect supply voltage!
An incorrect supply voltage may result in damage to the equipment.
■
Only operate the device with safety/protective extra-low voltage (SELV/PELV).
■
The sensor is a device of protection class III.
■
Only operate the device with an LPS (limited power source) in accordance with
IEC62368-1 or an NEC Class 2 power supply unit.
NOTICE
Equipment damage or unpredictable operation due to working with live parts!
Working with live parts may result in unpredictable operation.
■
Only carry out wiring work when the power is off.
■
Only connect and disconnect electrical connections when the power is off.
■
The electrical installation must only be performed by electrically qualified person‐
nel.
■
Standard safety requirements must be observed when working on electrical
systems!
■
Only switch on the supply voltage for the device when the connection tasks have
been completed and the wiring has been thoroughly checked.
■
When using extension cables with open ends, ensure that bare wire ends do not
come into contact with each other (risk of short-circuit when supply voltage is
switched on!). Wires must be properly insulated from each other.
■
Wire cross-sections in the supply cable from the user’s power system must be
selected in accordance with the applicable standards.
■
Operation in short-circuit protected network at max. 8A.
NOTE
Layout of data cables
■
Use shielded data cables with twisted-pair wires.
■
Implement proper and complete shielding concept.
■
To avoid interference, e.g., from switching power supplies, motors, clocked regula‐
tors, and contactors, always use cables and layouts that are suitable for EMC.
■
Do not lay cables over long distances in parallel with voltage supply cables and
motor cables in cable ducts.