8016441/2013-11-22•©SICKAG•Subjecttochangewithoutnotice 27
Electrical connection
AllelectricalconnectionsoftheISD400ProareconguredasM12round
connectors.
TheIP65protectionclassisonlyachievedusingscrewedplugconnectors.
AllelectriccircuitsconnectedtotheISD400Promustbeconguredas
PELVorSELVcircuits(PELV=protectiveextra-lowvoltage,SELV=safety
extra-lowvoltage).
Byusingappropriatecableentriesandwiring,youcanavoidinterference
fromdevicessuchasswitchingpowersupplies,motors,clockeddrives,and
contactors.
• Cablesshouldbelaidasfarawayaspossiblefromcableswithahigh
levelofradiatedemission.Takeadditionalmeasureswherenecessary,
e.g.separationbymeansofscreeningshields.
• Donotlaycablesparalleltoothercables,especiallynottodeviceswith
ahighlevelofradiatedemission,suchasafrequencyconverter.
• Donotlaycablesparalleltoenergycables.
Pleaseobservethefollowingwiringnotes:
• Acorrectandcompletecableshieldingconceptisrequiredfortrouble-
freeoperation.
• Thecableshieldmustbeconnectedatbothendsinthecontrolcabinet
andatthedevice.Thecableshieldofthepre-assembledcableiscon-
nectedtotheknurlednutandthusalsotothedevicehousing.
• Thecableshieldinthecontrolcabinetmustbeconnectedtotheopera-
tinggroundoveralargesurfacearea.
• Appropriatemeasuresmustbetakentopreventequipotentialbonding
currentsowingthroughthecableshield.
• Donotlaycablesparalleltoothercables,especiallynottodeviceswith
ahighlevelofradiatedemission,suchasafrequencyconverter.
1
2
4
3
1
2
4
3
90
90
Fig. 9: Cross cables at right angles