Addendum Operating Instructions Chapter 6
S3000 PROFINET IO/IOOF
8013291/YY95/2016-02-05 © SICK AG • Industrial Safety Systems • Germany • All rights reserved 15
Subject to change without notice
Configuration
6 Configuration
PROFINET IO network
An MRP domain and a NameOfStation must be named as per the PNO specification V2.3.
For this reason take into account the following naming convention during the configuration
of your PROFINET IO network:
The identifier comprises one or more words.
These words are separated using a [.].
The total length of the identifier is 1 to 240 characters.
The word length is 1 to 63 characters.
The identifier uses the following syntax:
Words comprise [a-z0-9-].
Words do not start with [-].
Words do not end with [-].
The first word must not have the form port-xyz or port-xyz-abcde
(a, b, c, d, e and x, y, z = 0 … 9).
Identifiers must not have the form n.n.n.n (n = 0 … 999).
Also take into account on naming an MRP domain:
The total length of the identifier must be 3, 7, 11, 15, 19, … characters.
S3000 PROFINET IO/IOOF
The configuration is performed in 3 steps:
1. Configuration PROFINET IO
2. Configuration PROFIsafe
3. Configuration of the S3000 PROFINET IO/IO8OF
Note