The PROFINET interface of the SIG200 has the following properties:
Characteristic Values
Transmission speed 100 Mbit/s
Maximum distance between nodes 100 m
Process data Max. 257 bytes input, 257 bytes output
Min. cycle time 1 ms
Asynchronous data Supported, see "Acyclic data", page 27
Compliant standard IEEE802.3u (100Base-Tx)
Conformance class Class B
Netload class II
Ethernet ports 2
PROFINET features Media redundancy (MRP), Network diagnostic (MIB/
SNMP), Topology detection, Port diagnostic (Up/Down),
Connection diagnostic (connection length measure‐
ment), I&M0…3, Auto device replacement, Reduction
ratio, OpenVAS tested
GSDML file Available in V2.2, V2.32, V2.33, V2.34
Any integration of SIG200 in a PROFINET PLC requires the use of the corresponding
GSDML file (General Station Description Markup Language).
Please download the GSDML file from www.sick.com. There are different versions for
different engineering tools available.
7.1.2.1 Device model
SIG200 PROFINET represents process data and acyclic data in the following slots:
The PROFINET slots have the following functions:
SIG200 CONFIGURATION
7
8017853/2019-06-06 | SICK O P E R A T I N G I N S T R U C T I O N | Sensor Integration Gateway - SIG200
19
Subject to change without notice