Parameters/address space
4.2 Parameters
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 02/2014, A5E03573289-AD
19
Parameter Value range Default Reconfiguration
in RUN
Scope with configuration
software, e.g.,
STEP 7 (TIA Portal)
GSD file
PROFINET IO
GSD file
PROFIBUS DP
Type/range of
measurement
• Deactivated
Thermal resistor
(4-wire connection)
Pt 100 standard
range
Yes Channel Channel
• Voltage ±50 mV
• Voltage ±80 mV
• Voltage ±250 mV
• Voltage ±1 V
Resistor
(2-, 3-, 4-wire connection)
• 150 Ω
• 300 Ω
• 600 Ω
• 3 kΩ
• 6 kΩ
Type/range of
measurement
Resistor (2-wire connection)
PTC
Thermal resistor
(4-wire connection)
Pt 100 standard
range
Yes Channel Channel
Type/range of
measurement
Thermal resistor
(2, 3, 4-wire connection)
• Pt 100 climatic range
• Pt 200 climatic range
• Pt 500 climatic range
• Pt 1000 climatic range
Thermal resistor
(4-wire connection)
Pt 100 standard
range
Yes Channel Channel
Thermal resistor
(2, 3, 4-wire connection)
• Pt 100 standard range
• Pt 200 standard range
• Pt 500 standard range
• Pt 1000 standard range