Parameters/address space
4.2 Parameters
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
18 Manual, 02/2014, A5E03573289-AD
4.2 Parameters
Parameters of the AI 4xRTD/TC 2-/3-/4-wire HF
The following table lists the configurable parameters. The effective range of the configurable
parameters depends on the type of configuration. The following configurations are possible:
● Distributed operation on PROFINET IO in an ET 200SP system
● Distributed operation on PROFIBUS DP in an ET 200SP system
When assigning parameters in the user program, use the WRREC instruction to transfer the
parameters to the module by means of data records, see section Parameter assignment and
structure of parameter data record (Page 52). The following parameter settings are possible:
Table 4- 3 Configurable parameters and their defaults (GSD file)
Parameter Value range Default Reconfiguration
in RUN
Scope with configuration
software, e.g.,
STEP 7 (TIA Portal)
GSD file
PROFINET IO
GSD file
PROFIBUS DP
Diagnostics:
Missing supply
voltage L+
• Disable
• Enable
D
isable Yes Channel Channel
1
Diagnostics:
Reference
junction
• Disable
• Enable
D
isable Yes Channel Module
Diagnostics:
Overflow
• Disable
• Enable
Disable Yes Channel Module
Diagnostics:
Underflow
• Disable
• Enable
Disable Yes Channel
Diagnostics:
Wire break
• Disable
• Enable
Disable Yes Channel Channel