Representation of analog values
B.3 Representation of analog values for resistance-type sensors
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 02/2014, A5E03573289-AD
65
B.3 Representation of analog values for resistance-type sensors
The following tables list the decimal and hexadecimal values (codes) of the possible
resistance-type sensor ranges.
Table B- 6 Resistance-type sensors from 150 to 6000
Values Resistance-type sensor range Range
Dec. Hex. 150 Ω 300 Ω 600 Ω 3000 Ω 6000 Ω
32767 7FFF > 176.38 > 352.77 > 705.53 > 3527.7 Ω > 7055.3 Ω Overflow
32511 7EFF 176.38 352.77 705.53 3527.7 Ω 7055.3 Ω Overrange
27649 6C01
27648 6C00 150 300 600 3000 Ω 6000 Ω Nominal range
20736 5100 112.5 225 450 2250 Ω 4500 Ω
1 1 5.43 mΩ 10.85 mΩ 21.70 mΩ 108.5 mΩ 217 mΩ
0 0 0 0 0 0 0
-32768 8000 (negative values are physically impossible) Underflow
1
1
If the resistors are not connected correctly or the conductor resistance is too high