Parameter data record
A.3 Switchable wire break check
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 02/2014, A5E03573289-AD
61
Switchable wire break check
Function
The "Switchable wire break check" is available for thermocouples. It switches off the wire
break check for the module.
This is required, for example, to calibrate thermocouples, since the test current necessary for
a wire break check leads to measurement errors during calibration.
The function has no effect on channels that are not assigned in the thermocouple mode.
Note
Startup and parameter reassignment
The wire break check is switched on again at each startup and during any parameter
reassignment of the module.
Switch-off via the user program
You can deactivate the wire break check using data record 237.
Table A- 12 Structure of data record 237, switchable wire break check
Deactivate wire break check
Activate wire break check