Parameters/address space
4.4 Scalable measuring range
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 02/2014, A5E03573289-AD
29
Rules
The measuring range center must be within the nominal range of the underlying
measuring range. It is specified in integers.
The scalable measuring range is spanned symmetrically over the measuring range
center. Depending on the resolution, various value ranges result (
, ).
The scalable measuring range is limited by underflow and overflow of the underlying
measuring range:
It is clipped at the underflow when it falls below the limit.
It is clipped at the overflow when it exceeds the limit (
).
Example
The following example illustrates the effect of scalable measuring ranges:
Scalable measuring range with 2 decimal places in hexadecimal S7 format
Scalable measuring range with 3 decimal places in hexadecimal S7 format
Scalable measuring range which is cut off at the overflow of the underlying measuring range (clipping)
Figure 4-4 Examples of scalable measuring ranges