Parameters/address space
4.4 Scalable measuring range
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
32 Manual, 02/2014, A5E03573289-AD
Parameters
The figure below shows the structure of the parameter.
If the corresponding bit is set to "1", the parameter is activated.
* x = 2 + (channel number x 8)
Figure 4-8 Structure of data record 235 - channel parameter byte x to x+7
Description of the parameters
Table 4- 9 Description of the parameters from data record 235
Parameter Description
Scalable measuring range enabled 1 = Function is active for this channel.
Clipping 1 = Scalable measuring range cut off at the overflow /
underflow of the underlying measuring range (see Figure
(Page 29)).
Resolution 2 or 3 decimal places
Measuring range center Temperature in whole °C / °F / K ("working point" for the
scaling)
Overflow/underflow Limits of the scalable measuring range