Interrupts/diagnostics alarms
5.3 Diagnostics alarms
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 02/2014, A5E03573289-AD
39
Diagnostics alarms
Error code
Meaning
Remedy
Parameter assignment
error
10
H
The module cannot evaluate parameters
for the channel: Module plugged in does
not match the configuration.
Incorrect parameter assignment.
Correct the configuration
(comparison of preset and actual
setup).
Correct the parameter assignment
(diagnostics wire break set only
with the permitted measuring
ranges).
Load voltage missing 11
H
Missing or insufficient supply voltage L+
Check supply voltage L+ on the
BaseUnit
Check BaseUnit type
Reference channel
error (reference
junction)
15
H
Reference temperature of the reference
junction for the TC channel being
operated with compensation is invalid.
Check BaseUnit type
Select correct reference junction
through parameter assignment
3
Check whether the reference
junction (reference channel of the
group 0, 1, 2, 3) is only assigned
once as the sender in the entire
setup.
Hardware interrupt lost 16
H
At least one hardware interrupt could not
be reported because there were too many
pending hardware interrupts.
Correct the program or the process
1
The alarm refers to the diagnostics and depends on the configured measuring range.
2
For resistor and thermal resistor measuring ranges with deactivated diagnostics for "Wire break", this is reported by the
"Violation of high limit" diagnostic.
3
Shared Device and diagnostics "Reference temperature": If the sender and receiver of the reference junction
temperature of a group are assigned to different IO controllers, you may need to download both configurations again in
the case of diagnostics. First download the configuration containing the receiver.