Analog value representation
4.3 Measuring ranges
2AI TC ST analog electronic module (6ES7134-4JB00-0AB0)
20 Manual, 04/2007, A5E01076883-01
Measuring range for thermocouple Type E
Table 4-4 SIMATIC S7 format: Type E measuring range in °C
Units
Type E in °C
Decimal Hexadecimal
Range
> 1200,0 32767 7FFF
H
Overflow
1200,0
:
1000,1
12000
:
10001
2EE0
H
:
2711
H
Overshoot range
1000,0
:
-270,0
10000
:
-2700
2710
H
:
F574
H
Nominal range
< -270,0 - 32768 8000
H
Underflow
Measuring range for thermocouple Type J
Table 4-5 SIMATIC S7 format: Type J measuring range in °C
Units
Type J in °C
Decimal Hexadecimal
Range
> 1450,0 32767 7FFF
H
Overflow
1450,0
:
1200,1
14500
:
12010
38A4
H
:
2EEA
H
Overrange
1200,0
:
-210,0
12000
:
-2100
2EE0
H
:
F7CC
H
Nominal range
< -210,0 - 32768 8000
H
Underflow