Analog value representation
4.3 Measuring ranges
2AI TC ST analog electronic module (6ES7134-4JB00-0AB0)
Manual, 04/2007, A5E01076883-01
21
Measuring range for thermocouple Type K
Table 4-6 SIMATIC S7 format: Type K measuring range in °C
Units
Type K in °C
Decimal Hexadecimal
Range
> 1622,0 32767 7FFF
H
Overflow
1622,0
:
1372,1
16220
:
13721
3F5C
H
:
3599
H
Overrange
1372,0
:
-270,0
13720
:
-2700
3589
H
:
F574
H
Nominal range
< -270,0 - 32768 8000
H
Underflow
Measuring range for thermocouple Type L
Table 4-7 SIMATIC S7 format: Type L measuring range in °C
Units
Type L in °C
Decimal Hexadecimal
Range
> 1150,0 32767 7FFF
H
Overflow
1150,0
:
900,1
11500
:
9001
2CEC
H
:
2329
H
Overrange
900,0
:
-200,0
9000
:
-2000
2328
H
:
F830
H
Nominal range
< -200,0 -32768 8000
H
Underflow
Measuring range for thermocouple Type N
Table 4-8 SIMATIC S7 format: Type N measuring range in °C
Units Type N in °C
Decimal Hexadecimal
Range
> 1550,0 32767 7FFF
H
Overflow
1550,0
:
1300,1
15500
:
13001
3C8C
H
:
32C9
H
Overrange
1300,0
:
-270,0
13000
:
-2700
32C8
H
:
F574
H
Nominal range
< -270,0 -32768 8000
H
Underflow