09.02 Connection
Siemens AG 6SE7087-6AK85-1AA0
3-5
Rectifier/Regenerating Unit Operating instructions
The units are designed for permanent connection to the system in keeping with DIN VDE 0160 Section 6.5.2.1.
Protective conductor connection: Min. cross-sectional area 10 mm
2
(see Table 3.2).
The conductor cross-sectional areas listed in Table 3.2 are maximum connectable cross-sections. The data is
given for multicore cable. The cross-sectional areas actually wired and the associated connection elements
must be selected according to the currently valid standards - e.g. DIN VDE 100 Part 523, DIN VDE 0276 Part
1000, UL, CSA, ....
Unit Order No. Mains DC link Protective conductor
Rated
input
Conductor
U1/L1, V1/L2,W1/L3
1U2/1T1, 1V2/1T2,
1W2/1T3
Conductor
C/L+, D/L-
Conductor
PE
voltage current max. max. max. max.
6SE70 (V) (A) mm
2 1)
AWG
2)
mm
2 1)
AWG
2)
mm
2 1)
AWG
2)
22-1EC85-1AA0 380 to 480 18 50
3)
1/0 50
3)
1/0 10 10
24-1EC85-1AA0 380 to 480 36 50
3)
1/0 50
3)
1/0 16 6
28-6EC85-1AA0 380 to 480 74 50
3)
1/0 50
3)
1/0 25 4
31-7EE85-1AA0 380 to 480 149 2x120 2x4/0 2x150 2x300 70 2/0
32-2EE85-1AA0 380 to 480 192 2x120 2x4/0 2x150 2x300 95 3/0
33-1EE85-1AA0 380 to 480 269 2x120 2x4/0 2x150 2x300 150 300
33-8EE85-1AA0 380 to 480 326 2x240 2x500 2x300 2x600 185 350
34-6EE85-1AA0 380 to 480 403 2x240 2x500 2x300 2x600 240 500
36-1EE85-1AA0 380 to 480 526 2x240 2x500 2x300 2x600 300 600
38-2EH85-1AA0 380 to 480 710 C 4x300
R 100x10
4x600 C 4x300
R 60x10
4x600 C 4x300
R 100x10
4x600
41-0EH85-1AA0 380 to 480 888 C 4x300
R 100x10
4x600 C 4x300
R 60x10
4x600 C 4x300
R 100x10
4x600
41-3EK85-1AA0 380 to 480 1156 C 4x300
R 100x10
4x600 C 6x300
R 100x10
6x600 C 4x300
R 100x10
4x600
41-3EK85-1AD0 380 to 480 1156 C 4x300
R 100x10
4x600 C 6x300
R 100x10
6x600 C 4x300
R 100x10
4x600
41-8EK85-1AA0 380 to 480 1542 C 4x300
R 100x10
4x600 C 6x300
R 100x10
6x600 C 4x300
R 100x10
4x600
41-8EK85-1AD0 380 to 480 1542 C 4x300
R 100x10
4x600 C 6x300
R 100x10
6x600 C 4x300
R 100x10
4x600
22-7FC85-1AA0 500 to 600 24 50
3)
1/0 50
3)
1/0 10 8
24-1FC85-1AA0 500 to 600 36 50
3)
1/0 50
3)
1/0 16 6
27-2FC85-1AA0 500 to 600 62 50
3)
1/0 50
3)
1/0 16 6
28-8FC85-1AA0 500 to 600 82 50
3)
1/0 50
3)
1/0 25 4
31-5FE85-1AA0 500 to 600 131 2x120 2x4/0 2x150 2x300 70 2/0
32-4FE85-1AA0 500 to 600 203 2x120 2x4/0 2x150 2x300 120 4/0
32-7FE85-1AA0 500 to 600 233 2x120 2x4/0 2x150 2x300 120 4/0
33-5FE85-1AA0 500 to 600 307 2x240 2x500 2x300 2x600 185 350
34-2FE85-1AA0 500 to 600 366 2x240 2x500 2x300 2x600 185 350
1) C=Cable, R=Rail
2) American Wire Gauge
3) Terminal connection area: Multicore10mm
2
to 50mm
2
AWG 8 to AWG 1/0
Stranded 3.5mm
2
to 35mm
2
AWG 12 to AWG 2