09.02  Start-Up 
Siemens AG    6SE7087-6AK85-1AA0 
4-35 
Rectifier/Regenerating Unit    Operating Instructions 
4.3.9  Function selection   (P052) 
Function selection is activated via parameter P052 and permits various special functions during the start-up 
phase. 
 
Access stage 2 (
P051 = 2) must be enabled and the rectifier/regenerating unit may only be in the "Run" (R) 
status. Apart from this, P053 must be set for parameter enable (e.g. P053=6). 
 
The following functions are available: 
  - Return from function selection  (P052 = 0) 
  - Generate factory setting  (P052 = 1) 
  - Initialization (MLFB setting)  (P052 = 2) 
  - Download  (P052 = 3) 
  - Hardware configuration  (P052 = 4) 
  - Drive setting  (P052 = 5) 
  - Forming  (P052 = 20) 
  - Circuit identification  (P052 = 21) 
  - Display modified parameters  (P052 = 22) 
 
The "Generate factory setting", "Forming", and "Circuit identification" functions are automatically reset on 
completion, i.e. P052 = 0 ("Return"). 
The other functions must be manually reset! 
 
4.3.9.1  Generate factory setting   (P052 = 1 or P970 = 0) 
This function is used to reset the parameter values, in accordance with a) the parameter list (dispatch status for 
the unit; see Section 5, column 4) and b) parameter P077 (see below). Only the settings of parameters P070 
(MLFB) and P077 (type of factory setting) remain unchanged. 
The MLFB-dependent parameters P071, P075 and P076 are set in accordance with the type of the 
rectifier/regenerating unit (see Section 4.3.9.2 "Initialization"). 
The parameters dependent on P077 are set in accordance with the table shown below. 
In the normal case (P070=0), the values listed in the parameter list in Section 5 are used as factory settings, so 
the table shown below does not have to be considered. 
For fast parameterization of special functions, using P077=1 to 6, an appropriate set of factory settings can be 
selected for certain parameters in accordance with the table shown below. In this manner, for example, certain 
terminals of the basic unit can be parameterized fast as sources for certain control word functions. 
The following table shows the factory settings for the parameters that are dependent on P077: 
 
Normal 
factory 
setting
 
Standard 
cubicle with
terminals 
Standard 
cubicle with 
PMU 
Standard 
cubicle with 
OP1S 
Standard 
cubicle with 
PMU as 
12-pulse slave 
Standard 
cubicle with 
OP1S as 
12-pulse slave
P077= 0  P077= 1  P077= 2  P077= 4  P077= 5  P077= 6 
Para- 
meters 
depend. 
on 
P077 
Designation of 
the parameter 
on OP1S 
Basic 
(i001) 
Res. 
(i002) 
Basic 
(i001) 
Res.
(i002)
Basic
(i001)
Res.
(i002)
Basic
(i001)
Res.
(i002)
Basic
(i001)
Res. 
(i002) 
Basic 
(i001) 
Res.
(i002)
P486  Src Current Setp  0  0  0  0  0  0  0  0  6002  0  6002  0 
P554  Src ON/OFF1  1010 1001 2001 1001 1003 1010 1003 2001 6001 1010 6001 2001 
P555 Src1 OFF2(electr.) 1010 1002 2001 1002 1003 1010 1003 2001 6001 1010 6001 2001 
P561 Src InvRelease 1 1 1 1 1 1 1 1 6001 1 6001 1 
P565 Src1 fault reset 0 1003 0 1003 0 0 0 0 0 0 0 0 
P566 Src2 fault reset  0  0  0  0 1004 0 1004 0 6001 0 6001 0 
P567 Src3 fault reset 2001 2001 2001 2001 0  0 2001 2001 2001 0 2001 2001 
P572 Src RegenRelease 1 1 1 1 1 1 1 1 6001 1 6001 1 
P575  Src No ExtFault1  1  1  1  1  1001 1001 1001 1001 1001 1001 1001 1001 
P583 Src 12-pulse mode 0 0 0 0 0 0 0 0 1 0 1 0 
P587 Src Master/Slave  0 0 0 0 0 0 0 0 1 0 1 0 
P588 Src No Ext Warn1  1  1  1  1  1002 1002 1002 1002 1002 1002 1002 1002 
P607  Trg Bit Warning  0   0  1001  1001  1001  1001  
The factory setting for P607.002 (responsible for the optional SCI1/2 module) is not affected by P077. 