09.02  Parameter List 
Siemens AG    6SE7087-6AK85-1AA0 
5-17 
Rectifier/Regenerating Unit    Operating Instructions 
PNU 
 
*
 
: Conf. 
    Par. 
OP1S parameter name 
 
Description 
Value range  
[phys. unit] 
Selection text 
Display 
Indices 
Factory- 
setting 
See 
Modify 
(access / 
status) 
5.9 Setpoint channel 
P486 
* 
Src Current Setp 
Setpoint source 
 
Parameter values: 
As per PZD wiring of the setpoint channel (see Section 4.3.1.3) 
 
Only effective if slave drive (control word 2, bit 27 =1) 
 
G/R parameter 
 
PNU=1E6Hex; Type=L2; Scaling: 1Hex 
=
∧
 1 
0 to 6005  2 
(0) 
3/    BR 
3/    BR 
P517  DC Volts Dev Lim 
Setpoint/actual-value deviation of Ud: 
If the deviation between the Ud setpoint and the actual Ud is considerable, 
the "Setpoint/actual-value deviation" message is generated (status word 1 
Bit 8 (r552)) 
Compare P518 (min. duration of deviation) 
 
RDS- parameter 
 
PNU=205Hex; Type=O2; Scaling: 1Hex 
=
∧
 0.01 
0.00 to 100.00 
[%] of  1.35
*
P071 
4 
2.00 
3/    BR 
3/    B 
P518 Deviation Time 
Min. deviation time: 
If there is a deviation (P517), the "Setpoint/actual-value deviation" message 
(status word 1 bit 8 (r552)) is generated after this minimum time has 
elapsed 
 
RDS parameter 
 
PNU=206Hex; Type=O2; Scaling: 1Hex 
=
∧
 0.01 
0.00 to 10.00 
[s] 
4 
0.10 
3/    BR 
3/    B 
 