09.02  Parameter List 
Siemens AG    6SE7087-6AK85-1AA0 
5-27 
Rectifier/Regenerating Unit    Operating Instructions 
PNU 
 
*
 
: Conf. 
    Par. 
OP1S parameter name 
 
Description 
Value range  
[phys. unit] 
Selection text 
Display 
Indices 
Factory- 
setting 
See 
Modify 
(access / 
status) 
5.11 Analog input/output 
P655 CUR AnaOutActVal 
Number of the parameters whose value is to be output at the analog output 
of the CUR, (terminal X102-14). 
 
PNU=28FHex; Type=O2; Scaling: 1Hex 
=
∧
 1 
0 to 999  - 
37 
2/    BR 
2/    BR 
P656  CUR AnaOut Gain 
Gain for the analog output of the CUR (terminal X102-14) 
 
P656 = desired analog output voltage at PWE=100%, if offset=0 
 
The output voltage is calculated with the following formula: 
U(out)= [(PWE/100%) 
*
 P656] + P657 
 
PNU=290Hex; Type=I2; Scaling: 1Hex 
=
∧
 0.01 V 
±320,00 
[V] 
- 
10.00 
2/    BR 
2/    BR 
P657 CUR AnaOutOffset 
Offset for the analog output on the CUR (terminal X102-14) 
The analog output can represent voltages of -10V to +10V. 
 
PNU=291Hex; Type=I2; Scaling: 1Hex 
=
∧
 0.01 V 
-100.00 to 100.00 
[V] 
- 
0.00 
2/    BR 
2/    BR 
P658 
* 
AnaOut Conf Curr 
Configuration of terminal X102-16 (actual current display) 
0  Output with correct sign 
(positive voltage: motoring current) 
(negative voltage: regenerative current) 
1  Output absolute value (positive voltage only) 
2  Signed output, inverted 
(positive voltage: regenerative current) 
(negative voltage: motoring current) 
3  Output of absolute value, inverted (negative voltage only) 
 
PNU=292Hex; Type=O2; Scaling: 1Hex 
=
∧
 1 
0 to 3 
 
signed 
 
 
absoluteVal 
inverted 
 
 
inv. absVal 
- 
0 
2/    BR 
2/    BR 
P660 SCI AnalogInConf 
Configuration of the SCI analog inputs; defines the kind of the input signals 
 
Parameter values  Terminals  Terminals 
    X428/3, 6, 9  X428/5, 8, 11 
  0:  -10 V ... + 10 V  - 20 mA ... + 20 mA 
  1:  0 V ... + 10 V  0 mA ... + 20 mA 
  2:    4 mA ... + 20 mA 
 
Notes: 
Only one signal can be wired per input; alternatively voltage or current 
signals can be evaluated. 
Voltage and current signals must be connected to different terminals. 
Settings 1 and 2 only allow unipolar signals, i. e. the internal process data 
are also unipolar. 
At setting 2 an input current < 2 mA causes a fault trip (broken wire proof) 
The offset scaling of the analog inputs is done via P662. 
 
i001:  Sl11  Slave 1, analog input 1 
i002:  Sl12  Slave 1, analog input 2 
i003:  Sl13  Slave 1, analog input 3 
i004:  Sl21  Slave 2, analog input 1 
i005:  Sl22  Slave 2, analog input 2 
i006:  Sl23  Slave 2, analog input 3 
 
Condition: 
The related SCB board must be reported via P090 and P091, respectively 
 
PNU=294Hex; Type=O2; Scaling: 1Hex 
 =
∧
 1 
0 to 2  6 
0 
3/    BR 
3/    BR 