Parameter List  09.02 
5-16  Siemens AG    6SE7087-6AK85-1AA0 
  Rectifier/Regenerating Unit    Operating Instructions 
PNU 
 
*
 
: Conf. 
    Par. 
OP1S parameter name 
 
Description 
Value range  
[phys. unit] 
Selection text 
Display 
Indices 
Factory- 
setting 
See 
Modify 
(access / 
status) 
P366 
* 
Auto Restart 
Auto restart after power outage 
If the power fails at one of the terminals U1/L1, V1/L2, W1/L3, 1U2/1T1, 
1V2/1T2 1W2/1T3, X9.1 and X9.2, or if the voltage is not within the 
permissible tolerance range and
  the DC link voltage has dropped beneath 
the P074 
*
 1.35 
*
 P071 threshold, the S/F unit responds as follows:: 
 
0  Auto restart inhibited 
No automatic restart; the corresponding fault message (F003, 
F004, F005, F007, F009 or F010) is triggered. 
 
1  Acknowledgment following power outage 
The rectifier/regenerating unit enters status 
o
008 (switch-on 
inhibit) or 
o
009 (switch on/off from the I/O keys of the PMU). On 
power recovery, a new ON command must be given to enable 
the DC link to re-charge. The inverter is not
 automatically 
restarted by the WEA (auto restart) function. 
 
2  Restart following power recovery and pre-charging of the DC 
link 
During the power outage, the controllers and firing pulses of the 
PZD R/R are inhibited. The rectifier/regenerating unit enters 
status 
o
010. On recovery of the voltage, the DC link is charged 
again as quickly as possible (see Section 4.3.10.1). 
 
Important: The necessary external measures must be taken to guarantee 
safety on an automatic restart! 
 
PNU=16EHex; Type=O2; Scaling: 1Hex 
=
∧
 1 
0 to 2 
 
 
 
 
 
 
 
OFF 
 
 
 
 
ON Reset 
 
 
 
 
 
 
 
ON Always 
- 
0 
3/    BR 
3/    BR 
P408 Caps FormingTime 
Forming time of the DC link 
This parameter is used when forming the DC link (P052=20). 
 
RDS parameter 
 
PNU=198Hex; Type=O2; Scaling: 1Hex 
=
∧
 0.1 
1.0 to 600.0 
[min] 
4 
10.0 
2/   ABR 
2/   AB 
P409 Contactor Delay 
Closing delay of the line contactor 
Closing of the line contactor is delayed by the time set here with respect to 
the "Switch on" command. 
 
This parameter can be used to implement time grading when energizing the 
line contactors of several drive units in order to prevent the inrush currents 
of the autotransformers for regenerative mode overloading a supply 
transformer. 
 
PNU=199Hex; Type=O2; Scaling: 1Hex 
=
∧
 0.1 
0.0 to +120.0 
[s] 
- 
0.0 
3/   BR 
3/   B 
 