Start-Up  09.02 
4-8  Siemens AG    6SE7087-6AK85-1AA0 
  Rectifier/Regenerating Unit    Operating Instructions 
P571 = 0001
P318 = 
P408 = 
r000
 
≤
 
o
009
P613 = 1001
P571 = 1004
P319 =
P318 = 
Regen.
transformer?
yes
no
Permanent
reduction
yes
Wait to
Ud<50V
Forming
Idle time
of converter
>1year
yes
no
no
(see r006)
P052 = 20
P key
Switch-on
 
 
Mode variants: 
a)  The system voltage in the regenerative branch is 
stepped up by an (auto) transformer in order not to 
have to reduce the link voltage in regenerative mode 
b) Permanent reduction
 of the link voltage by phase 
angle control in rectifier mode to always be able to 
feed power back into the system 
P318 Reduced DC link voltage setpoint (e.g. = 80 %) 
P571 = 0001 Permanent selection of reduced voltage 
c)  Reduction of the DC link voltage only for regenerative 
feedback operation to make full use of the line voltage 
in infeed operation and to obviate the need for an 
autotransformer for regenerative feedback. (See also 
Chapter 4.3.10.2) 
c1) Externally required reduction
 of the DC link voltage 
by external control (using the control word command 
"Ud reduction requested") 
P318 reduced DC link voltage setpoint (e.g. = 80 %) 
P571 = 1004 on selection of the reduction via terminal 
X101-12 (binary input 4) 
P613 = 1001 message "DC link voltage reduced" 
output at alarm relay X104-17/18 (ready 
for regenerative feedback) 
P319  Hysteresis for the message "DC link voltage 
reduced" (ready for regenerative feedback) 
c2) Automatic reduction
 of the DC link voltage depending 
on the DC link current (only implemented on Software 
Version 3.2 and higher and not shown in the adjacent 
diagram): 
  If the DC link current falls below threshold P321 in 
infeed direction, the command for Ud reduction is 
generated internally. The load current drawn must still 
remain positive for long enough before it changes 
direction after falling below P321 to permit a drop of 
Ud to the required value. The current-dependent Ud 
reduction therefore only works if the appropriate load 
cycle applies. 
  Relevant parameters: P318, P319, P321, P322, P323 
 
 
 
Forming the DC link (if necessary; see Section 
4.3.9.6) 
- The rectifier/regenerating unit must be in status 
o
009 or 
less (give SWITCH OFF command!). 
- Set P408 (forming time: 1.0 to 600.0 minutes). 
- Select function (P052 = 20) 
- Press the P key on the PMU 
- Switch on: Press the I key on the PMU 
- Forming of the DC link takes place  
- Following the forming process, the status display is 
activated. 
 