09.02 Start-Up
Siemens AG 6SE7087-6AK85-1AA0
4-39
Rectifier/Regenerating Unit Operating Instructions
4.3.9.3 Download or upread (P052 = 3)
P052 has to be set to 3 when a "download" (write) or "upload" (read) has to be carried out for the parameters of
the rectifier/regenerating unit at the basic unit interface (SST1) using USS protocol (e.g. using D or OP1S).
“Upread/Download" can be selected in the following statuses: "Switch-on inhibit" (008), "Ready-to-switch-on"
(009) or "Fault" (007).
Procedure:
P052 = 3 Function selection “Upread/Download
P key The operating display appears(021)
- Using a PC at the basic device interface SST1 and an appropriate application program (e.g.
DriveMonitor), it is possible to read and change all parameters independently of their
operating state and access level (P051).
P052 = 0 Function selection Return
P key
After return, the operating display appears, "Switch-on inhibit" (008) or "Ready-to-switch-on"
(009)