Parameter List 09.02
5-14 Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
P323
*
Rel.RedCD V(Cur)
Release of current-dependent DC reduction
0: current-dependent U
d
reduction blocked
1: current-dependent U
d
reduction released
(see also P318, P321, P322)
PNU=143Hex; Type=02; Scaling: 1Hex
=
1
0 to 1 -
0
3/ BR
3/ BR
P329 PreCharge Time
DC link pre-charging time
RDS parameter
PNU=149Hex; Type=O2; Scaling: 1Hex
=
1
0 to 9999
[ms]
4
500
3/ BR
3/ BR
P330 Discharge Time
DC link discharge time
An even parameter value causes abrupt lowering. With effect from software
version 4.5, an odd parameter value causes the Ud setpoint to ramp down
with Ud reduction controlled by STW1, bit11 (see Section 4.3.1.1 and
4.3.10.2).
With the command OFF1 and current-dependent Ud reduction, P330 is
active in all cases.
RDS parameter
PNU=14AHex; Type=O2; Scaling: 1Hex
=
1
0 to 9999
[ms]
4
2000
3/ BR
3/ BR