EasyManua.ls Logo

Siemens 6SE7038-2EH85-1AA0

Siemens 6SE7038-2EH85-1AA0
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
09.02 Parameter List
Siemens AG 6SE7087-6AK85-1AA0
5-25
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
P618
*
Trg Current Lim.
Destination wiring of the status bit "Current limit active"
(status word 2, bit 18)
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken-wire proof).
Parameter values, indices: as P600
PNU=26AHex; Type=L2; Scaling: 1Hex
=
1
0 to 4212 2
0
3/ BR
3/ BR
P619
*
Trg Bit Ext Flt1
Destination of the status bit 'External fault 1' (status word 2, bit 19)
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
Parameter values, indices: as P600
PNU=26BHex; Type=L2; Scaling: 1Hex
=
1
0 to 4212 2
0
3/ BR
3/ BR
P620
*
Trg Bit Ext Flt2
Destination of the status bit 'External fault 2'
(status word 2, bit 20)
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
If an ON command is active, L-level causes fault trip after 200 msec.
Parameter values, indices: as P600
PNU=26CHex; Type=L2; Scaling: 1Hex
=
1
0 to 4212 2
0
3/ BR
3/ BR
P621
*
Trg Bit ExtWarn
Destination of the status bit 'External warning'
(status word 2, bit 21)
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
Parameter values, indices: as P600
PNU=26DHex; Type=L2; Scaling: 1Hex
=
1
0 to 4212 2
0
3/ BR
3/ BR
P622
*
Trg Bit i2t Inv
Destination of the status bit 'Warning unit overload'
(status word 2, bit 22);
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
Parameter values, indices: as P600
PNU=26EHex; Type=L2; Scaling: 1Hex
=
1
0 to 4212 2
0
3/ BR
3/ BR
P623
*
Trg BitFltTmpInv
Destination of the status bit 'Fault unit overtemperature'
(status word 2, bit 23
Note:
For issuing the message via a terminal the active status (bit has H-level) is
inverted (broken wire proof).
Parameter values, Indices: as for P600
PNU=26FHex; Type=L2; Scaling: 1Hex
=
1
0 to 4212 2
0
3/ BR
3/ BR
https://www.aotewell.com
AoteWell Automation Sales Team
Sales@aotewell.com
AoteWell LTD
Buy Siemens PLC HMI Drives at AoteWell.com
https://www.aotewell.com

Table of Contents

Related product manuals