7SR242 Duobias Commissioning & Maintenance Guide 
©2010 Siemens Protection Devices Limited     Chapter 6 Page 10 of 57 
1.5 Binary Inputs 
 
The operation of the binary input(s) can be monitored on the ‘Binary Input Meters’ display shown in ‘Instruments 
Mode’. Apply the required supply voltage onto each binary input in turn and check for correct operation. 
Depending on the application, each binary input may be programmed to perform a specific function; each binary 
should be checked to prove that its mapping and functionality is as set as part of the Scheme Operation tests.  
Where the pick-up timers associated with a binary input are set these delays should be checked either as part of 
the scheme logic or individually. To check a binary pick-up time delay, temporarily map the binary to an output 
relay that has a normally open contact. This can be achieved in the Output Matrix sub-menu by utilising the BI n 
Operated settings. Use an external timer to measure the interval between binary energisation and closure of the 
output contacts. Similarly, to measure the drop-off delay, map to an output relay that has a normally closed 
contact, time the interval between binary de-energisation and closure of the output contacts. 
Note
. The time measured will include an additional delay, typically less than 20ms, due to the response time of 
the binary input hardware, software processing time and the operate time of the output relay.  
 
BI Tested  DO 
Delay 
Measure
d 
PU 
Delay 
Measured  Notes (method of initiation) 
1            
2            
3            
4            
5            
6            
7            
8            
9            
10            
11            
12            
13            
14            
15            
16            
17            
18            
19