7SR242 Duobias Commissioning & Maintenance Guide
©2010 Siemens Protection Devices Limited Chapter 6 Page 27 of 57
2.4 Restricted Earth fault (64H)
Figure 2-6 Restricted Earth Fault
Voltage Inputs: n/a
Current Inputs: I
G1 ,
I
G2
Disable: 50G, 51G, 50BF
Map Pickup LED: 64H-n - Self Reset
The external stabilising resistor value should be measured and compared to that specified in the settings data.
Both values should be recorded.
Element Settings Data: R
STAB
Value R
STAB
Measured
64H-1
64H-2
The relatively high value of stabilising resistance R
STAB
will often interfere with secondary current injection when
using a digital test set. It is normal practice in these cases to short circuit the resistor to allow testing, the shorting
link should be removed after testing.