7SR242 Duobias Commissioning & Maintenance Guide 
©2010 Siemens Protection Devices Limited     Chapter 6 Page 19 of 57 
2.1.4  Definite Time Overcurrent    (50) 
If DTL setting is small, gradually increase current until element operates. 
If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, check operation 
 Apply 2x setting current if possible and record operating time 
 
Phas
e 
Dir. Is  
(Amps) 
DTL 
(sec) 
P.U. Current 
Amps 
Operate Time 
2 x Is 
NOTES 
I
L1
(I
A
) 
 
I
L2
(I
B
) 
 
I
L3
(I
C
) 
   
 
 
 
Check correct indication, trip output, alarm contacts, waveform record. 
 
2.1.5  Inverse Time Overcurrent   (51) 
It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the 
Pickup Config sub-menu in the Output Config menu as this will allow the Pick-up LED to operate for the function. 
Gradually increase current until Pickup LED operates. 
Apply 2x setting current and record operating time, 
Apply 5x setting current and record operating time. 
Compare to calculated values for operating times 
 
Operate Current  Operate Time 
Ph. Dir  Char. 
(NI EI VI 
LTI, DTL) 
Is 
(A) 
TM 
P.U. 
(Amps) 
D.O. 
(Amps) 
2 x Is 
(sec) 
5 x Is 
(sec) 
NOTES 
I
L1
(I
A
) 
  
I
L2
(I
B
) 
  
 
P.U. 
D.O. 
& 
TIMIN
G 
TESTS 
I
L3
(I
C
) 
    
  
 
 
Calculated Timing values in seconds for TM =1.0 
Curve  2 xIs  5 xIs 
IEC-NI 10.03 4.28 
IEC-VI 13.50 3.38 
IEC-EI 26.67 3.33 
IEC-LTI 120.00 30.00 
ANSI-MI 3.80 1.69 
ANSI-VI 7.03 1.31 
ANSI-EI 9.52 1.30 
Note that the operate time may be subject to the Minimum op time setting for the element and/or may have a 
Follower DTL applied.