7SR242 Duobias Commissioning & Maintenance Guide
©2010 Siemens Protection Devices Limited Chapter 6 Page 30 of 57
46BC Setting 1P unbalance current
(% of 3P current)
20% 75%
25% 100%
30% 129%
35% 161%
40% 200%
46BC Setting 3P balanced current (A) 1P unbalance current (A) Measured Unbalance
current
46BC-1
46BC-2
Apply 1A 1P unbalance current without 3P balanced current. Measure 46BC operating time.
46BC Delay setting Measured
46BC-1
46BC-2
2.5.1.1 Element Blocking
Elements can be blocked by operation of a Binary Input Inhibit or by operation of the 46BC-n U/I Guard element.
This functionality should be checked.
Element BI Inhibits U/I Guard NOTES
46BC-1
46BC-2