3-Wire Grounded Wye, 3-Element Direct
The configuration requires that the transformer secondary star-point is
grounded. The phase-to-ground voltages must be within the meter’s range.
Volts Mode
= 4W-Wye
Single Phase Connection Diagram
Connect the two voltage phases (180° apart) to the V1 and V2 inputs, and
the CT outputs to the I1 and I2 input pairs. Unused meter inputs are
grounded.
Volts Mode
= Single
V
1
V
2
V
3
V
ref
I
11
I
12
I
21
I
22
I
31
I
32
2A
LINE
LOAD
A
B
C
N
PF angle
= 0.9 (25° Lag)
I
c
I
b
I
a
V
c
120°
V
a
V24
b
V1 V2
V3
Vref
I11
I12
I21
I22
I31
I32
2A
LINE
LOAD
A
B
N
PF angle
= 0.9 (25° Lag)
Ib
Ia
V
a
V18
b