EasyManua.ls Logo

Siemens 9200 - Configurable Settings - Part 2; Modbus Scaling and Digital Outputs; Display and Security Settings

Siemens 9200
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
Notes
1
For a meter with the Megawatt option, PTS must be set to “x1000.”
2
ION compatible protocol for use with an WinPM.Net system and
other ACCESS meters.
3
The units displayed on the front panel are Wh, VAh, and VARh with actual
values of kWh, kVAh, and kVARh respectively.
kWh REc. and kVARh Rec. are represented by a lit “minus” (negative
value) LED.
4
In Ext 1 or Ext 2 mode, the digital outputs are reserved for digital control.
5
Time Constant, sometimes called kT, is the number of units (kWh, kVAh,
kVARh) per output transition. The digital output uses KY pulsing. This
means that the relay changes from open to closed or from closed to open
whenever kT units have been measured (20 transitions/second maximum).
Modbus Scaling
Voltage Scale
0.001, 0.01, 0.1, 1, 10, 100,
1000
10
Current Scale
0.001, 0.01, 0.1, 1, 10, 100,
1000
10
Power Scale
0.001, 0.01, 0.1, 1, 10, 100,
1000
1
Neutral Scale
0.001, 0.01, 0.1, 1, 10, 100,
1000
10
Digital Outputs
Output Mode Digital
#1
(k)Wh Del., (k)VAh, (k)VARh Del.,
(k)Wh Rec., (k)VARh Rec. See note
3
Ext 1
4
, Ext 2
4
(k)Wh
3
Time Constant 1 (kT)
5
0.1 – 999.9
(only 1 digit after the decimal pt.
permitted)
1.0
Output Mode Digital
#2
(k)Wh Del., (k)VAh, (k)VARh Del.,
(k)Wh Rec., (k)VARh Rec. See note
3
Ext 1
4
, Ext 2
4
(k)VARh
3
Time Constant 2 (kT)
5
0.1 – 999.9
(only 1 digit after the decimal pt.
permitted)
1.0
Display
Display Scroll Time 0 – 30 seconds (0 = disable) 0
Display Refresh Period 1 – 6 seconds 2
Security
Password 0 – 9999 0
String Description Range (Values) Default
PUS
PCS
PCS
PPS
PPS
PnS
PnS
out1
out1
tc1
tc1
out2
out2
tc2
tc2
dS
r
c
dUPd
dUPd
PSEt

Table of Contents

Other manuals for Siemens 9200

Related product manuals