3 Activate manually î Alarm organization control unit (î Remote transmission)
− LED Ë ’Evacuation’
− Extinguishing horn
− Illuminated warning panel
− Fire control installations, if existing
− Main valve
Upon expiry of the evacuation period:
î Sector valve
Message and LED Ì ’Extinguishing released’ (after acknowledge-
ment)
After ’Reset’:
î all alarm- and reference messages must be erased
possibly fault ’extinguishing NOT ready’ + ’Glass broken’
4 Activate signal ’Extinguishing ac-
tivated’ (if existing)
î Alarm organization control unit (î Remote transmission)
− LED Ì ’Extinguishing released’
− Extinguishing horn
− Illuminated warning panel
− Fire control installations, if existing
After ’Reset’:
î all alarm- and reference messages must be erased
possibly fault ’extinguishing NOT ready’
In addition:
If emergency operation link E3G110 has been used
Ü Set control unit to ’Emergency operation’ (keep ’Restart’ key on the CPU depressed)
Test function
The following devices or functions are activated
5
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
Activate fire detectors in extin-
guishing SECTION
Note:
The detectors in the extinguis-
hing SECTION must be divided
between 2 different lines or mo-
dules.
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
î Emergency alarm at AlgoPilot ’CT11’ (î Remote transmission)
− LED Ê ’Fire detector activated’
− LED Ë ’Evacuation’
− Extinguishing horn
− Illuminated warning panel
− Main valve
Upon expiry of the delay period:
î Sector valve
− Message and LED Ì ’Extinguishing released’