6.2 Individual control functions
Control functions
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Comment
1
Check evacuation time
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Dependent on parameterization
î must correspond to the parameterized time
Ñ
Ñ
Ñ
Ñ
2
ÑÑÑÑÑÑ
ÑÑÑÑÑÑ
ÑÑÑÑÑÑ
ÑÑÑÑÑÑ
Check alarm horn switch-off
function
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Dependent on parameterization
î may only be possible either from the operating unit extinguishing
’B3Q440’ or the operating unit extinguishing ’B3Q440’ and AlgoPilot
’CT11’
î Switch-off must always be possible except during the ’Evacuation’
phase
î Check whether alarm horn cannot be switched off during ’Evacuation’
Ñ
3
ÑÑÑÑÑÑ
Check illuminated warning panel
switch-off function
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Dependent on parameterization
î either active until ’Reset’
or active until switched off separately via the operating unit extinguis-
hing ’B3Q440’
Ñ
4
ÑÑÑÑÑÑ
Check the duty cycle of main-/
and sector valve
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Dependent on parameterization
î either active until ’Reset’
or active during the time specified
Ñ
5
ÑÑÑÑÑÑ
Check line monitoring
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
î Induce a short circuit or open line for all peripheral equipment in quies-
cent state connected and check whether in each case a fault results
î With ’valve lines’ it is essential to induce open line and short circuit
Ñ
Ñ
Ñ
6
ÑÑÑÑÑÑ
ÑÑÑÑÑÑ
ÑÑÑÑÑÑ
Check ZONE affiliation
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
î In each detector ZONE belonging to the extinguishing SECTION acti-
vate 1 detector and check whether the extinguishing horn is activated
Dependent on parameterization
î In each detector ZONE belonging to the extinguishing SECTION, acti-
vate 2 (or 3) detectors and check whether the ’Evacuation’ phase is
initiated
Ñ
Ñ
Ñ
7
ÑÑÑÑÑÑ
ÑÑÑÑÑÑ
ÑÑÑÑÑÑ
Check ’Blocking’ function via
AlgoPilot ’CT11’ / list of functions
’SECTION’
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
î choose list of functions ’SECTION’ and check following functions:
− autom. & man. activation of extinguishing BLOCKING / ENABLE
− Extinguishing ß REVISION / terminate
− Extinguishing ß TEST / terminate
Here the corresponding LEDs Ê, Ë at the operating unit extinguishing
’B3Q440’ and AlgoPilot ’CT11’ must always on
Ñ
8
ÑÑÑÑÑÑ
Check ’Blocking’ function via
operating unit extinguishing /
keys À, Á
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
î Check at the extinguishing control panel whether by means of both
keys À, Á activation of extinguishing can be blocked accordingly
Here the corresponding LEDs Ê, Ë at the operating unit extinguishing
’B3Q440’ and AlgoPilot ’CT11’ must always on
6.3 Notes
Use of valve actuators
Ensure that the minimum trigger current (comply with manufacturers’ instructions) can also be
achieved without difficulty even with emergency power operation (operating voltage 23.5V).
Balance the difference between the ’internal resistance valve actuators’ (e.g. 1.5 Ω) and the
’minimum line impedance’ (16Ω) with series resistor.
Operation with emergency operation link E3G110
Never plug-in or un-plug the supply cable or I-bus flat cable on the module when power is
switched on.
Ensure that the detection line only contains detectors which belong to the extinguishing SEC-
TION.
Important
When using the E3G110 with collective line module E3M080 only use E3M080 from Index
’BC’ onwards.