EasyManua.ls Logo

Siemens CPU 312C

Siemens CPU 312C
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
$GGUHVVLQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
8-4 A5E00105492-03
The byte address depends on the module start address.
The bit address is the number printed on the module.
Insert the first digital module into slot 4 so that it has default start address 0. The
start address of every subsequent digital module will be incremented by 4 per slot
(see diagram under 6ORWEDVHGPRGXOHDGGUHVVLQJ
The figure below shows you how the addresses of the individual channels of a
digital module are obtained.
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
Byte address:
start address of modules
Byte address:
start address of modules + 1
Bit address
Figure 8-2 Addresses of the I/O of digital modules