EasyManuals Logo

Siemens CPU 312C Hardware And Installation Guide

Siemens CPU 312C
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #144 background imageLoading...
Page #144 background image
&RPPLVVLRQLQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
9-32 A5E00105492-03
 'LUHFW'DWD([FKDQJH
5HTXLUHPHQW
In 67(3 V 5.x or later, you can configure "Direct data exchange" for PROFIBUS
nodes. CPUs 31x-2 DP/31xC-2 DP can participate in direct data exchange both as
a sending or receiving station.
'HILQLWLRQ
"Direct data exchange" is a special communication relationship between
PROFIBUS-DP nodes.
Characteristic of direct data exchange is that PROFIBUS DP nodes "listen" on the
bus for data a DP slave returns to its DP master. This mechanism allows "Listening
stations" (receivers) direct access to modified input data of remote DP slaves.
$GGUHVVDUHDV
In your 67(3 configuration of the relevant peripheral input addresses, specify
which address area of the receiving station is to receive data requested from the
sending station.
A CPU 31x-2 DP/31xC-2 DP can operate as a:
DP slave sending station
receiving station, as DP slave or DP master, or as CPU not integrated in a
master system.

Table of Contents

Other manuals for Siemens CPU 312C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 312C and is the answer not in the manual?

Siemens CPU 312C Specifications

General IconGeneral
BrandSiemens
ModelCPU 312C
CategoryProcessor
LanguageEnglish

Related product manuals