&RQILJXULQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
5-19
 &RQILJXULQJDQ6ZLWK8QJURXQGHG5HIHUHQFH3RWHQWLDO
1RW&38[&
,QWURGXFWLRQ
If you install an S7-300 with ungrounded reference potential, any interference
currents that occur are dissipated via an RC system to the ground conductor/local
ground integrated into the CPU.
1RWH
An S7-300 with a CPU 31xC cannot be configured ungrounded.
$SSOLFDWLRQ
In extended systems, the S7-300 may require configuration with grounded
reference potential due to ground-fault monitoring. This is the case, for example, in
chemical industry and power stations.
8QJURXQGHGUHIHUHQFHSRWHQWLDORI&38DQG'3
The diagram illustrates an S7-300 configuration with floating reference potential
M
M
L+
M
10M
<100 nF
3
2
1
Figure 5-8 Creating an ungrounded reference potential on a CPU
7KHGLDJUDPLOOXVWUDWHVXQGHUQXPEHU
 If you implement an ungrounded reference potential in your CPU: Use a
screwdriver with 3.5 mm blade width and push the grounding slide contact forwards
in the direction of the arrow until it snaps into place.
 Ground of internal CPU circuitry
 Rail

Table of Contents

Other manuals for Siemens CPU 312C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 312C and is the answer not in the manual?

Siemens CPU 312C Specifications

General IconGeneral
BrandSiemens
ModelCPU 312C
CategoryProcessor
LanguageEnglish

Related product manuals