S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
12-12 A5E00105492-03
 6KLHOGLQJRI&DEOHV
3XUSRVHRIWKHVKLHOGLQJ
A cable is shielded to attenuate the effects of magnetic, electrical and
electromagnetic interference on the cable.
2SHUDWLQJSULQFLSOH
Interference currents on cable shielding is diverted to ground conductive
interconnection between the shielding and the cabinet. To avoid interference as a
result of these currents, it is imperative to provide a low-impedance connection to
the protective conductor.
6XLWDEOHFDEOHV
Whenever possible, use cables equipped with a shielding braid. Shielding density
should be at least 80%. Avoid cables with film shielding, because the film can be
easily damaged by tensile or pressure stress, thus reducing its shielding effect.
+DQGOLQJRIWKHVKLHOGLQJ
Note the following points on handling the shielding:
Always use metal clamps to mount shielding braid. The clamps must contact a
large area of the shielding and provide appropriate contact force.
Directly behind the cabinet's cable entry, terminate the shielding on a shielding
bus. Then, route the cable to the module; however, do not connect the shielding
once again to ground in this place.
In installations outside of cabinets (e.g. for wall-mounting) you can also
terminate the shielding on a cable duct.

Table of Contents

Other manuals for Siemens CPU 312C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 312C and is the answer not in the manual?

Siemens CPU 312C Specifications

General IconGeneral
BrandSiemens
ModelCPU 312C
CategoryProcessor
LanguageEnglish

Related product manuals