Accessories
8.11 Sine-wave filter
Power Module PM240-2
150 Hardware Installation Manual, 01/2020, A5E33294624B AL
Table 8- 16 Assignment table for 690 V Power Modules
Power Module
Output reactor
Frame size
Article number
Power [kW]
Article number
FSD 6SL3210-1PH21-4 . L0
6SL3210-1PH22-0 . L0
6SL3210-1PH22-3 . L0
11
15
18.5
JTA:TEU 2532-0FP00-4EA0
6SL3210-1PH22-7 . L0
6SL3210-1PH23-5 . L0
6SL3210-1PH24-2 . L0
22
30
37
JTA:TEU 9932-0FP00-4EA0
FSE 6SL3210-1PH25-2 . L0
6SL3210-1PH26-2 . L0
45
55
JTA:TEU 9932-0FS00-0EA0
FSF 6SL3210-1PH28-0 . L0
6SL3210-1PH31-0 . L0
75
90
JTA:TEU 9932-1FC00-1BA0
FSF 6SL3210-1PH31-2 . L0
6SL3210-1PH31-4 . L0
110
132
JTA:TEU 9932-0FV00-1BA0
FSG 6SL3210-1PH31-7CL0
6SL3210-1PH32-1CL0
6SL3210-1PH32-5CL0
160
200
250
JTA:TEU 4732-0FA00-0BA0
8.11 Sine-wave filter
The sine-wave filter limits the voltage gradient and the capacitive recharging currents which
generally occur in converter operation. Therefore, when a sine-wave filter is used, longer
screened motor cables are possible and the motor lifetime reaches the same values which
are achieved when the motor is connected directly to the mains.
When using a sine-wave filter, observe the following restrictions:
Operation is only permissible with pulse frequencies from 4 kHz ... 8 kHz (sine-wave filter
from 160kW only 4 kHz).
It must be ensured that the automatic pulse frequency reductions are deactivated.
The converter power is reduced by 5%.
The output frequency must not exceed 150 Hz.
Operation and commissioning may only be performed with the motor connected because
the sine-wave filter is not no-load proof.
An output reactor is not required.
NOTICE
Damage to the sine-wave filter if it is not activated during commissioning
The sine-wave filter may be damaged if it is not activated during commissioning.
Activate the sine-wave filter during commissioning via parameter p0230.
Activate the sine-wave filter during commissioning according to the electric
specifications.

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals