Outputs
12 universal inputs / outputs U1...U12 with the following output functions (10-bit DA
converter):
Voltage output, analog
Type Range (over range) Resolution Output current
AO 0-10V 0...10V (-0.05…10.6V) 1mV Max. 1mA
AO 0-10V
standard
0...100%
0% = 0V, 100% = 10V
(-0.05...10.6 V)
0.01% Max. 1mA
Relay output (outputs DO1...DO4)
External supply line fusing
Non-renewable fuse
Circuit breakers
Max. 10 A, slow
Max. 13 A, characteristic B, C, D as per EN60898
Switching voltage AC/DC Max. AC 250 V / DC 30 V
Min. AC/DC 12 V
Current load AC NO contact: Max. 4 A resistive, 3 A inductive (cos phi
0.6)
NC contact: max. 2 A resistive, 1.5 A inductive (cos phi
0.6)
Min. 1 mA at AC 250 V
Min. 10 mA at AC 12 V
Current on make AC NO contact: Max. 10A (1s)
NC contact: Max. 3A (1s)
Current load DC NO contact: Max. 3A resistive at DC 30V
NC contact: Max. 1A resistive at DC 30V
Min. 10 mA resistive at DC 12V
Response / release time 7ms / 3ms typical
Contact life at AC 250 V (reference values)
At 0.3 A resistive
NO contact at 3A resistive
NC contact at 2A resistive
Reduction factor for inductive load (cos phi = 0.6)
5 x 10
5
switching cycles
1 x 10
5
switching cycles
1 x 10
5
switching cycles
0.6
Insulating strength between relay contacts and system
electronics (reinforced insulation).
AC 3750V, as per EN 60730-1
CAUTION
No overvoltage protection is used when switching inductive loads
Risk of heavy electromagnetic disturbances and lower contact life when no overvoltage
protection is used when switching inductive loads.
● When switching inductive loads (e.g. contactors or electric motors) it is strongly
recommended to use suitable overvoltage protection devices to avoid heavy
electromagnetic disturbances and to ensure the specified contact life.