Periphery board (250p) FCI2016
Configuration input power and battery
1
12 | 46
Building Technologies
A6V10315038_f_en_
--
Siemens Industry,
Inc.
2016
-
02
-
1.4.3 X302 Power supply 2 terminal block
Terminal block X302 may only be used for an additional PS300 when the system
requirements exceed 300 W. The housing (3HU) is the only housing that is capable of
having two PS300 supplies connected at the same time. No power supply (170 W)
may be connected to terminal block X302.
Terminal X301 must always have a power supply
connected. When a single power
supply is used, it must be connected to terminal X301.
Check whether jumper X305 is in position 2-3 before PS300 #1 is connected to X301
or #2 to X302. Make sure line voltage is not present on the system, and that the
breaker in the panel is off. Both power supplies need to be connected before line
voltage is switched on at the panel. X301 and X302 should never be
connected/disconnect with line voltage present. Batteries may only be connected after
the system is brought up on line voltage power.
Pin Designation Description
1 BROO
(White) AC low signal. Signals when the supply system
connection drops below AC 102 V.
2 PSSI
(Green) Power supply status indication. Used by the
periphery board to know the health of the power supply.
3 GND (Black) Return (ground)
4 +24 V (Red) DC +24 V system supply
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
1.4.4 X305 jumper – Power supply 2 on/off
This jumper is used to configure the periphery board for one or two power supplies.
The factory setting may only be changed when a second power supply (300 W) in an
housing (3HU) is supported.
X305 Jumper position Function Meaning
1 - 2
Deactivated
PS 2 300 W
Default setting; for power supply (170 W) and a single power
supply (300 W).
2 - 3
Activated
PS 2 300 W
For a second power supply (300 W) in an housing (3HU).
The power supply is activated and is monitored by the system.
1
2
3
1
2
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FCI2017-U1 and is the answer not in the manual?

Siemens FCI2017-U1 Specifications

General IconGeneral
BrandSiemens
ModelFCI2017-U1
CategorySmoke Alarm
LanguageEnglish

Related product manuals