Page #22 background image
Periphery board (250p) FCI2016
Tec
hnical data
1
22 | 46
Building Technologies
A6V10315038_f_en_
--
Siemens Industry,
Inc.
2016
-
02
-
Bell follower input Plug strip X1001
Voltage DC 24 V filtered or full wave
Curent Max. 4 mA
Design Voltage surge protection
Detector circuits Terminal strips X1401 circuit card 1, circuit 1
X1402 circuit card 1, circuit 2
Output voltage DC 24 V, filtered
Number of integrated circuit
cards
1
Output current per integrated
circuit card
Max. 500 mA
Addressable devices per
integrated circuit card
Max. 252
Connectable circuits per
integrated circuit card
2 style 6 or 4 style 4 (mixed variants are possible)
Protocol FDnet/C-NET
Circuit resistance Max. 180 Ω
Capacity 500 nF per circuit
Cable types All (twisted recommended)
You will find detailed specifications in the following
documents:
A6V10315013 for Desigo
A6V10333396 for Cerberus PRO
Connectable devices See 'List of compatibility'
Monitored for Ground fault
Short circuit
Open circuit
Circuit capacitance
Design Short-circuit-proof
Voltage surge protection
Open circuit
Power limited
Relay contacts Plug strip X1201
Design Relay output
Break or make contact
Nonpower limited
Alarm and trouble active in degraded mode
operation
Switching voltage DC 30 V or AC 120/240 V ohmic
Switching current
5 A @ DC 30 V or AC 120 V
4 A @ AC 240 V