54BTechnical data FDOOT221, FDOOT241-x / -Ax
119 |
2015-11-04
Permissible operating temperature:
● FDOOT221 -10…+60 °C
● FDOOT241-8/-9/-A3/-A4 -25…+70 °C
● FDOOT241-A -35…+70 °C
● FDOOT241-A5 -25…+70 °C
● FDOOT241-A9 -35…+70 °C
Storage temperature:
● FDOOT221 / FDOOT241-x/-Ax -30…+75 °C
● FDOOT241-A -35…+75 °C
● FDOOT241-A9 -35…+75 °C
Air humidity ≤95 % rel.
Protection categories (IEC 60529):
● Base FDB2x1/FDB2x1-AA/FDB2x2, IP43
● with base attachment FDB291 IP43
● Base FDB2x1 and sealing element
FDBZ295
IP44
● Base adapter FDB241, FDB299, FDB251,
FDB281
IP44
● Sounder base FDSB29x IP43
● Base attachment wet FDB295 IP44
Electromagnetic compatibility:
● 1 MHz…2 GHz 50 V/m
Permissible wind speed:
● FDOOT221 Max. 5 m/s
● FDOOT241-x/-Ax Max. 20 m/s
Color ∼RAL 9010 pure white
European standards ● EN 54-7
● EN 54-17
● EN 54-5 for FDOOT241-x/-Ax
● CEA 4021