7BSpecifications
54BTechnical data FDOOT221, FDOOT241-x / -Ax
8
119 |
138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
Ambient conditions
Permissible operating temperature:
FDOOT221 -10…+60 °C
FDOOT241-8/-9/-A3/-A4 -25…+70 °C
FDOOT241-A -35…+70 °C
FDOOT241-A5 -25…+70 °C
FDOOT241-A9 -35…+70 °C
Storage temperature:
FDOOT221 / FDOOT241-x/-Ax -30…+75 °C
FDOOT241-A -35…+75 °C
FDOOT241-A9 -35…+75 °C
Air humidity ≤95 % rel.
Protection categories (IEC 60529):
Base FDB2x1/FDB2x1-AA/FDB2x2, IP43
with base attachment FDB291 IP43
Base FDB2x1 and sealing element
FDBZ295
IP44
Base adapter FDB241, FDB299, FDB251,
FDB281
IP44
Sounder base FDSB29x IP43
Base attachment wet FDB295 IP44
Electromagnetic compatibility:
1 MHz…2 GHz 50 V/m
Permissible wind speed:
FDOOT221 Max. 5 m/s
FDOOT241-x/-Ax Max. 20 m/s
Mechanical data
Color ∼RAL 9010 pure white
Standards
European standards EN 54-7
EN 54-17
EN 54-5 for FDOOT241-x/-Ax
CEA 4021