4BMounting / Installation
34BPreparing detector base FDB22x for installing an FDOOT241-A3 or FDOOT241-A4
5
75 |
138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
5.4 Preparing detector base FDB22x for installing an
FDOOT241-A3 or FDOOT241-A4
The point detectors FDOOT241-A3 and FDOOT241-A4 can be used to replace
detectors from the AnalogPLUS or SIGMALOOP detector families.
You will find details in the 'List of compatibility'.
Use one of the FDB221, FDB221-AA, or FDB222 detector bases.
1. Use the table below to determine the resistance which corresponds to the
existing detector type.
Resistor connection
R = ∞Ω
Do not install a resistor
2. Install the resistor. See figure 'Resistor connection'.
If the detector is replacing a DO1131A, SDF1200, or SDF2200, do not
install a resistor.
3. Use the auxiliary terminal DBZ1190-AA for multiple assignment. See figure
'Resistor connection'.
D 113 AT2
DO 1131AT
DT1131A
SDF 0031
SDT2100
+
-
+
-
+
-
R
DO113 A1
R = Ω
+
R = 10 kΩ ±2 kΩ (0,25 W)
R = 18 kΩ ±2 kΩ (0,25 W)
R = 27 kΩ ±2 kΩ (0,25 W)
1

Table of Contents

Other manuals for Siemens FD20

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FD20 and is the answer not in the manual?

Siemens FD20 Specifications

General IconGeneral
BrandSiemens
ModelFD20
CategorySecurity Sensors
LanguageEnglish

Related product manuals