7BSpecifications
56BTechnical data FDT221, FDT241
8
132
| 138
007004_t_en_--
2015-11-04
Device characteristics
Response sensitivity Depending on parameter set
Detector diagnosis With detector exchanger and tester
FDUD292 or intelligent detector tester
FDUD293
Ambient conditions
Permissible operating temperature Depending on parameter set
Storage temperature -30…+75 °C
Air humidity 95 % rel.
Protection category (EN 60529/IEC 60529):
Bases FDB221/FDB221-AA/FDB222, IP43
With base attachment FDB291 IP43
Base FDB221 and sealing element
FDBZ295
IP44
Base attachment humid FDB295 IP44
Sounder base FDSB291 IP43
Electromagnetic compatibility:
1 MHz…2 GHz 50 V/m
Static response temperature:
Parameter set BR and BS 78…82 °C
Parameter set A1R and A1S 58…62 °C
Mechanical data
Color ∼RAL 9010 pure white
Standards
European standards EN 54-5
EN 54-17